Standard type
Features
Environment | Cooling method | Functions |
Indoor | Peltier | Display |
Certificates/Approvals
EU RoHS2 | China RoHS | CE | UL | CSA | PSE |
Model/Specification
Model | OCE-100FSC-A1 | OCE-100FSC-A2 | OCE-200FSC-A1 | OCE-200FSC-A2 | |
Type of mounting | Lateral mounting | ||||
Cooling method | Fan-cooled air agitation | ||||
Cooling capacity*1 | 90/100W | 180/200W | |||
Rated voltage(50/60Hz) | Single phase 100VAC | Single phase 200VAC | Single phase 100VAC | Single phase 200VAC | |
Current consupmtion*2 | Rated | 2.1/2.0A | 1.1/1.0A | 3.9/3.8A | 2.0/1.9A |
Max. | 2.3/2.2A | 1.2/1.1A | 4.3/4.2A | 2.2/2.1A | |
Starting current | 7.5A | 4.0A | 11.5A | 8.0A | |
Power consumption*2 | Rated | 210/200W | 210/200W | 390/380W | 390/380W |
Max. | 230/220W | 230/220W | 435/425W | 435/425W | |
Working temperature | 0 to +50℃ | ||||
Working humidity | Not exceeding 80%RH,free from condensation | ||||
Noise | 52dB(A) | 56dB(A) | |||
Display | Innter temperature/Alarm code/Operation lamp/Alarm lamp | ||||
Temperature setting range | +10 to +50℃(Initial setting +30℃) | ||||
Function | Off-temperature alarm,Maintenance reminder,Detection of fan shutdown on cooling side,Detection of temperature sensor disconnection,Detection of abnormal temperature at power supply | ||||
External output | 240V 1.5A | ||||
Environmental standard | RoHS2 | RoHS | RoHS2 | ||
Operating method | ON/OFF control DIF:3℃ | ||||
Drainage water*3 | Max.15ml/h | Max.30ml/h | |||
Color | Beige(10GY9/1 corresponding) | ||||
Dimensions(mm)*4 | W265×H241×D177 | W265×H381×D177 | |||
Weight | 6.0kg | 9.8kg |
*1 Nominal cooling capacity with +30℃ in working temperature.
*2 Nominal values at 30℃ temperature when both inside and outside are indicated in "Rated" and nominal values at 10℃ outside and 30℃ inside temperatures are indicated in "Max".
*3 Maximum amount of condensation water discharged when ambient temperature is 50℃ and humidity is 80%RH.
*4 Projections are excluded.
*2 Nominal values at 30℃ temperature when both inside and outside are indicated in "Rated" and nominal values at 10℃ outside and 30℃ inside temperatures are indicated in "Max".
*3 Maximum amount of condensation water discharged when ambient temperature is 50℃ and humidity is 80%RH.
*4 Projections are excluded.
- Supply voltage should be within the fluctuation range of 10% from the rated voltage.
Contents of page
OCE-100FSC-A1/A2
Cooling capacity
90/100W
A complete set of supply
●BOXCOOL:1 pc ●Fixing bolt:4 pcs ●Spring washer:4 pcs ●Plain washer:4 pcs
●Nut:4 pcs ●Drain hose:1 pc(2m) ●Terminal board:1 pc ●Instruction manual:1 copy
●Nut:4 pcs ●Drain hose:1 pc(2m) ●Terminal board:1 pc ●Instruction manual:1 copy
Consumable parts
Filter at suction port |
BCF-S1(2pcs/set) |
Cooling capacity
180/200W
A complete set of supply
●BOXCOOL:1 pc ●Fixing bolt:4 pcs ●Spring washer:4 pcs ●Plain washer:4 pcs
●Nut:4 pcs ●Drain hose:1 pc(2m) ●Terminal board:1 pc ●Instruction manual:1 copy
●Nut:4 pcs ●Drain hose:1 pc(2m) ●Terminal board:1 pc ●Instruction manual:1 copy
Cousumable parts
Filter at suction port |
BCF-S2(2pcs/set) |
Performance diagram
Dimensional drawing
Mounting cutout
Cautions
・Do not use this product in a place where inflammable gasses, corrosive gasses or any matters that may destroy insulation present.
・The site of use should be free from vibration and impact.
・Make sure that electrical wiring work is done by qualified electrician.
・Be sure to install the product perpendicularly within 1 degree tolerance.
・Reverse thermoelectric effect is not available with this product.
・Any packaging damage may be a cause of malfunction. Make sure that the packaging is not damaged on delivery and contact your supplier.
・For outdoor use, please consider outdoor use models (OCE-100BEC-AW,OCE-200BEC-AW)
・The site of use should be free from vibration and impact.
・Make sure that electrical wiring work is done by qualified electrician.
・Be sure to install the product perpendicularly within 1 degree tolerance.
・Reverse thermoelectric effect is not available with this product.
・Any packaging damage may be a cause of malfunction. Make sure that the packaging is not damaged on delivery and contact your supplier.
・For outdoor use, please consider outdoor use models (OCE-100BEC-AW,OCE-200BEC-AW)