Go to global navigation

Read the article

Go to local navigation

Go to footer



Climate control equipment


Condensate-free type


Drain evaporator is integrated.
No troublesome work for drain management.

OCE-FSCJ

Features

Environment of use Cooling method Type Function
Indoor Thermoelectric Condensate-free Display

Certificates/Approvals

EU RoHS2 EU RoHS China RoHS CE UL CSA PSE

Model/Specification

Model OCE-100FSCJ-A1 OCE-100FSCJ-A2 OCE-200FSCJ-A1 OCE-200FSCJ-A2
Type of mounting Lateral mounting
Cooling method Fan-cooled Cool Air Agitation
Drain evaporation method Evaporation at low temperature by heater
Cooling capacity*1 90/100W 180/200W
Evaporation capacity*2 50ml/h(at the temperature+30℃ and 80%RH humidity)
Rated voltage(50/60Hz) Single phase 100VAC Single phase 200VAC Single phase 100VAC Single phase 200VAC
Current consumption*3 Rated 2.8/2.7A 1.4/1.3A 4.6/4.5A 2.3/2.2A
Max. 3.0/2.9A 1.5/1.4A 4.9/4.8A 2.6/2.4A
Starting current 8.5A 4.5A 13.0A 9.0A
Power consumption*3 Rated 280/270W 280/270W 450/440W 450/440W
Max. 300/290W 300/290W 495/485W 495/485W
Working temperature 0 to+50℃
Working humidity 80%RH or less, free from condensation
Noise 52dB(A) 56dB(A)
Display Innter temperature/Alarm code/Operation lamp/Alarm lamp
Temperature setting range +10 to +50℃(Initial setting +30℃)
Functions Off-temperature alarm, Maintenance reminder, Detection of fan shutdown on cooling side, Detection of temperature sensor disconnection, Detection of abnormal temperature at power supply,
Overheat protection for evaporation unit:Thermal fuse (fusing at 75℃,replacing), Detection of tank over flow
External output 240V 1.5A
Applicable standard Environment RoHS2 RoHS RoHS2
Operating method ON/OFF control DIF:3℃
Operation control for evaporation Thermostat-controlled ON/OFF
Color Beige (10GY9/1 equivalent)
Dimensions(mm)*4 W265×H335×D177 W265×H475×D177
Weight 7.5kg 11.0kg
*1 Nominal cooling capacity with +30℃ in working temperature.
*2 The value shows the performance under the given conditions and may be lessened depending on the environment of usage.
*3 Nominal values at 30℃ temperature both inside and outside are indicated in "Rated" and nominal values at 10℃ inside and 30℃ outside temperatures are indicated in "Max". These values are based on condition that both of cooling and dehumidifying operations are executed.
*4 Projections are excluded.
  • Supply voltage should be within the fluctuation range of 10% from the rated voltage.


Product lineup

OCE-100FSCJ-A1/A2

OCE-100FSCJ

Cooling capacity

90/100W

A complete set of supply

BOXCOOL : 1 unit Fixing bolt : 4 pcs. SP washer : 4 pcs. Plain washer : 4 pcs. 
Nut : 4 pcs. Terminal board : 1 pc. Instruction manual : 1 copy
* Drain hose is not included.

Maintenance parts

Suction port filter Evaporator suction port filter
BCF-S1 (2 pcs/set) BCF-S3 (1 pc.)

Performance chart

能力グラフ

Dimensional drawing

外形寸法図

Mounting cutout


パネルカット図


OCE-200FSCJ-A1/A2

OCE-200FSCJ

Cooling capacity

180/200W

A complete set of supply

BOXCOOL : 1 unit Fixing bolt : 4 pcs. SP washer : 4 pcs. Plain washer : 4 pcs. 
Nut : 4 pcs. Terminal board : 1 pc. Instruction manual : 1 copy
* Drain hose is not included.

Maintenance parts

Suction port filter Evaporator suction port filter
BCF-S2 (2 pcs/set) BCF-S3 (1 pc.)

能力グラフ

外形寸法図

パネルカット図


Cautions

・Do not use this product in a place where flammable or corrosive gasses, or any matters that can destroy insulation generate or permeate.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Install this product perpendicularly within a tolerance of 1 degree.
・This product cannot be used so as to invert cooling and heating operations.
・Make sure that the packaging is not damaged on delivery. Any packaging damage can lead to breakdown of the product. Please contact us immediately if any damage is found.
・This product is for indoor use only. For outdoor use, please see BOXCOOL outdoor types OCE-100BEC-AW and OCE-200BEC-AW.