Temperature control system Inversion type with power supply
Temperature control system specifically designed for BOXCOOL
Enables automatic control of cooling temperature with high accuracy
Enables automatic control of cooling temperature with high accuracy
Features
Environment of use | Function | |
Indoor | Display | Wide range of supply voltages |
Certificates/Approvals
EU RoHS2 | China RoHS | CE | UL | CSA | PSE |
Model/Specifications
Model | OCE-TCR12075WL | OCE-TCR24150WL | OCE-TCR24300WL | OCE-TCR24600WL | |
Temperature control method | Auto-tuning PID controller ON/OFF control | Auto-tuning PID controller ON/OFF control | |||
Output control method | Polarity reversion type Linear voltage control/PWM control Output | ||||
Thermoelectric module output rating | ±12VDC 6.3A | ±24VDC 6.3A | ±24VDC 14.0A | ±24VDC 27.0A | |
Fan motor output rating | 12VDC 0.8A | 24VDC 0.8A | |||
Power supply voltage (50/60Hz) | Single phase 100-240VAC | ||||
Max. power consumption | 150VA | 250VA | 550VA | 950VA | |
Temperature sensor (option) | Resistance temperature detector JIS Pt100 3-wire type Thermocouple (T/K) | ||||
Communication function | USB2.0 RS-485 | ||||
Temperature setting range | -50.0 to +80.0℃ | ||||
Temperature control accuracy *1 | ±0.1℃ | ||||
Display resolution | 0.1℃ | ||||
Working temperature | 0 to +40℃ | ||||
Working humiidity | Max. 90%RH, free from condensation | ||||
Upper and lower limit setting of control output | Arbitrary setting by voltage level | ||||
Safety function | Fuse (double protection on primary side) Alarm buzzer Self diagnosing (Upper and lower limit error detection, power failure detection, thermistor off-temperature detection) |
||||
External input/output | Analog output 1 point, Communication/RS-485 1 point, Communication/USB 2.0 1 point, Event contact output 1 point, Alarm contact output 1 point |
||||
Alarm display | Green/Orange LED Buzzer output | ||||
Input/output terminal board | Output/Signal input 7P (Peltier output 2P/Fan output 2P/Temperature sensor input 3P) Power supply output 3P (AC input/FG) |
Output 8P (Peltier output 2P/Fan output 2P/temperature sensor input 3P) (Peltier output 2P x 3/Fan output 2P) Signal input 3P (Temperature sensor input) Power supply input 3P (AC input/FG) |
|||
Connector | 10P for events RS-485 6P USB port | ||||
Noise | 37dB | 54dB(MAX) | 55dB(MAX) | ||
Conformity to standards | Environment | RoHS2 | |||
Dimensions (mm) *2 | W150×H105×D216 | W220×H105×D316 | |||
Weight | 2.5kg | 4.2kg | 4.6kg | ||
Applicable BOXCOOL models | OCE-F15P-D12 OCE-F15F-D12 OCE-L15P-D12 OCE-L15F-D12 |
OCE-F40P-D24 OCE-F40F-D24 OCE-L40P-D24 OCE-L40F-D24 |
OCE-F80P-D24 OCE-F80F-D24 OCE-F80LA-D24 OCE-F80LT-D24 OCE-L80P-D24 OCE-L80F-D24 OCE-L80LA-D24 OCE-L80LT-D24 |
OCE-F120F-D24 OCE-F160LA-D24 OCE-F160LT-D24 OCE-L160LA-D24 OCE-L160LT-D24 |
*1 Accuracy of temperature sensor is not included. The value is based on constant working temperature condition and varies depending on working environment.
*2 Excluding rubber feet, terminal board and projections
*2 Excluding rubber feet, terminal board and projections
OCE-TCR12075WL/24150WL
A complete set of supply
Temperature control system : 1 unit
Thermistor for thermoelectric module protection : 2 pcs. 2 m long
Event connector 10P : 1 pc.
Connector for RS485 6P : 1 pc. Instruction manual : 1 copy
* For 100VAC power supply
Power cable WH-A-M4-2 is available as an optional extra.
Thermistor for thermoelectric module protection : 2 pcs. 2 m long
Event connector 10P : 1 pc.
Connector for RS485 6P : 1 pc. Instruction manual : 1 copy
* For 100VAC power supply
Power cable WH-A-M4-2 is available as an optional extra.
Dedicated software
Dedicated software for enabling operation and data recording by PC is available to download free.
OCE-TCR24300WL/24600WL
A complete set of supply
Temperature control system : 1 unit
Thermistor for thermoelectric module protection : 2 pcs. 2 m long
Event connector 10P : 1 pc.
Connector for RS485 6P : 1 pc. Instruction manual : 1 copy
Power cable WH-A-M4-2 is available as an optional extra.
Thermistor for thermoelectric module protection : 2 pcs. 2 m long
Event connector 10P : 1 pc.
Connector for RS485 6P : 1 pc. Instruction manual : 1 copy
Power cable WH-A-M4-2 is available as an optional extra.
Dedicated software
Dedicated software for enabling operation and data recording by PC is available to download free.
Example of connection
Cautions
・Do not use this product in a place where flammable or corrosive gasses, oil fume or any matters that can destroy insulation generate or permeate.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Indoor use only.
・Make sure that the packaging is not damaged on delivery. Any packaging damage can lead to breakdown of the product. Please contact us immediately if any damage is found.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Indoor use only.