Standard (External mounting) - UL listed
No. 1 enclosure heat exchanger brand in Japan
Versatile lineup gives freedom of choice
Versatile lineup gives freedom of choice
Environment of use | Type of mounting | Cooling method |
Indoor | Eternal lateral mounting | Air cooling |
Certificates/Approvals
EU RoHS2 | China RoHS | CE | UL | CSA | PSE |
Model/Specifications
Model | OC-17S-A100 | OC-17S-A200 | OC-12S-A100 | OC-12S-A200 | OC-15S-A100 | OC-15S-A200 | |
Type of mounting | External lateral mounting | ||||||
Cooling capacity *1 | 8/10W/K | 10/12W/K | |||||
Rated voltage*2 | Single phase 100 to 120VAC | Single phase 200 to 230VAC | Single phase 100 to 120VAC | Single phase 200 to 230VAC | Single phase 100 to 120VAC | Single phase 200 to 230VAC | |
Rated current consumption *3 | 0.50A/0.45A | 0.25A/0.23A | 0.50A/0.45A | 0.25A/0.23A | 0.50A/0.45A | 0.25A/0.23A | |
Rated power consumption *3 | 44/42W | ||||||
Working temperature | -10 to +70℃, ice-free | ||||||
Working humidity | 20 to 85%RH, free from condensation | ||||||
Noise | 59dB(A) | 58dB(A) | |||||
Conformity to standards | Safety | UL1995 | |||||
Environmental | RoHS2 | ||||||
Dimensions (mm)*4 | W170×H680×D60 | W200×H480×D66 | W150×H590×D90 | ||||
Weight | 6.2kg | 5.8kg | 6.1kg |
Model | OC-28S-A100 | OC-28S-A200 | OC-31S-A100 | OC-31S-A200 | OC-30S-A100 | OC-30S-A200 | |
Type of mounting | External lateral mounting | ||||||
Cooling capacity *1 | 16/20 W/K | 25/30 W/K | |||||
Rated voltage*2 | Single phase 100 to 120VAC | Single phase 200 to 230VAC | Single phase 100 to 120VAC | Single phase 200 to 230VAC | Single phase 100 to 120VAC | Single phase 200 to 230VAC | |
Rated current consumption *3 | 1.00A/0.90A | 0.50A/0.45A | 1.00A/0.90A | 0.50A/0.45A | 1.40A/1.20A | 0.70A/0.60A | |
Rated power consumption *3 | 88/84W | 100/90W | |||||
Working temperature | -10 to +70℃, ice-free | ||||||
Working humidity | 20 to 85%RH, free from condensation | ||||||
Noise | 62dB(A) | 63dB(A) | 67dB(A) | ||||
Conformity to standards | Safety | UL1995 | |||||
Environmental | RoHS2 | ||||||
Dimensions (mm)*4 | W280×H590×D90 | W310×H680×D60 | W300×H650×D90 | ||||
Weight | 10.7kg | 11.0kg | 12.5kg |
Model | OC-20S-A100 | OC-20S-A200 | OC-37S-A100 | OC-37S-A200 | OC-40S-A100 | OC-40S-A200 | |
Type of mounting | External lateral mounting | ||||||
Cooling capacity *1 | 34/43 W/K | 35/42 W/K | 60/80 W/K | ||||
Rated voltage*2 | Single phase 100 to 120VAC | Single phase 200 to 230VAC | Single phase 100 to 120VAC | Single phase 200 to 230VAC | Single phase 100 to 120VAC | Single phase 200 to 230VAC | |
Rated current consumption *3 | 1.40A/1.20A | 0.70A/0.60A | 2.80A/2.40A | 1.40A/1.20A | 2.80A/2.40A | 1.40A/1.20A | |
Rated power consumption *3 | 100/90W | 200/180W | 200/180W | ||||
Working temperature | -10 to +70℃, ice-free | ||||||
Working humidity | 20 to 85%RH, free from condensation | ||||||
Noise | 66dB(A) | 68dB(A) | 69dB(A) | ||||
Conformity to standards | Safety | UL1995 | |||||
Environmental | RoHS2 | ||||||
Dimensions (mm)*4 | W200×H714×D160 | W382×H650×D90 | W400×H714×D160 | ||||
Weight | 14.5kg | 16.1kg | 28.3kg |
*1 Nominal value when the temperature difference between inside and outside the control panel is 20K
*2 This product is designed for single phase, 100VAC or 200VAC supply voltage only. Please consult us for other supply voltages.
*3 Values based on our measurement under the temperature and humidity conditions of +25℃ and 50%RH
*4 Excluding the terminal block and the filter guard
*2 This product is designed for single phase, 100VAC or 200VAC supply voltage only. Please consult us for other supply voltages.
*3 Values based on our measurement under the temperature and humidity conditions of +25℃ and 50%RH
*4 Excluding the terminal block and the filter guard
OC-17S-A100/A200
Cooling capacity
8/10 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 120 sq. : 1 pc. Screws for filter guard : 4 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-120 |
1pc/set | OG-17 FIN | 1 set | OF-S1 | 1 pc. | FM-11938M -MV-00 |
1 pc. |
Cooling capacity
10/12 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 120 sq. : 1 pc. Screws for filter guard : 4 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-120 | 1pc/set | OG-12 FIN | 1 set | OF-S1 | 1 pc. | FM-11938M -MV-00 |
1 pc. |
Cooling capacity
10/12 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 120 sq. : 1 pc. Screws for filter guard : 4 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-120 | 1pc/set | OG-15 FIN | 1 set | OF-S1 | 1 pc. | FM-11938M -MV-00 |
1 pc. |
Cooling capacity
16/20 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 120 sq. : 1 pc. Screws for filter guard : 4 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-120 | 1pc/set | OG-28 FIN | 1 set | OF-S1 | 1 pc. | FM-11938M -MV-00 |
1 pc. |
Cooling capacity
16/20 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 120 sq. : 1 pc. Screws for filter guard : 4 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-120 | 1pc/set | OG-31 FIN | 1 set | OF-S1 | 1 pc. | FM-11938M -MV-00 |
1 pc. |
Cooling capacity
25/30 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 150 sq. : 1 pc. Screws for filter guard : 4 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-150 | 1pc/set | OG-30 FIN | 1 set | OF-S2 | 1 pc. | FM-15055M -MV-00 |
1 pc. |
Cooling capacity
34/43 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 150 sq. : 1 pc. Screws for filter guard : 4 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-150 | 1pc/set | OG-20H FIN | 1 set | OF-S2 | 1 pc. | FM-15055M -MV-00 |
1 pc. |
Cooling capacity
35/42 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 150 sq. : 2 pc. Screws for filter guard : 8 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-150 | 1pc/set | OG-37 FIN | 1SET | OF-S2 | 1 pc. | FM-15055M -MV-00 |
1 pc. |
Cooling capacity
60/80 W/K (50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 150 sq. : 2 pcs. Screws for filter guard : 8 pcs.
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Warning label (Electric shock) : 1 pc. Instruction manual : 1 copy
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-150 | 1pc/set | OG-40H FIN |
1 set | OF-S2 | 1 pc. | FM-15055M -MV-00 |
1 pc. |
Related products
Cautions
・Locate BOXFAN at least 150 mm away from adjacent components or walls to keep smooth air circulation between inside and outside the enclosure. Failure to this will lead to performance decline.
・Electrical connection should be made via an appropriate circuit breaker.
・This product is for indoor use only.
・Do not use this product in a place where flammable or corrosive gasses or any matters that can destroy insulation generate or permeate.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Make sure that the packaging is not damaged on delivery. Any packaging damage can lead to breakdown of the product. Please contact us immediately if any damage is found.
・Electrical connection should be made via an appropriate circuit breaker.
・This product is for indoor use only.
・Do not use this product in a place where flammable or corrosive gasses or any matters that can destroy insulation generate or permeate.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Make sure that the packaging is not damaged on delivery. Any packaging damage can lead to breakdown of the product. Please contact us immediately if any damage is found.