CE-marked External mounting
External mounting type with CE marking
Environment of use | Type of mounting | Cooling method |
Indoor | External lateral mounting | Air cooling |
Certificates/Approvals
EU RoHS2 | China RoHS | CE | UL | CSA | PSE |
Model/Specifications
Model | OC-12S-A200-CE | OC-28S-A200-CE | OC-37S-A200-CE | |
Type of mounting | External lateral mounting | |||
Cooling capacity *1 | 10/12W/K | 16/20W/K | 35/42W/K | |
Rated voltage*2 | Single phase 200 to 230VAC | |||
Rated current consumption *3 | 0.20-0.24A/0.18-0.21A | 0.40-0.48A/0.36-0.42A | 1.12-1.41A/1.14-1.21A | |
Rated power consumption *3 | 44/42W | 88/84W | 200/180W | |
Working temperature | -10 to +70℃, ice-free | |||
Working humidity | 20 to 85%RH, free from condensation | |||
Noise | 58dB(A) | 62dB(A) | 68dB(A) | |
Conformity to standards |
EMC Directive | EN55011、EN61000-3-2、EN61000-3-3、EN61000-6-2 | ||
Low Voltage Directive | EN60204-1 | |||
Environment | RoHS2 | |||
Dimensions (mm)*4 | W200×H480×D66 | W280×H590×D90 | W382×H650×D90 | |
Weight | 5.8kg | 10.7kg | 16.1kg |
*1 Nominal value when the temperature difference between inside and outside the control panel is 20K
*2 This product is designed for single phase 200 to 230VAC range.
*3 Values based on our measurement under the temperature and humidity conditions of +25℃ and 50%RH
*4 Excluding the terminal block and the filter guard
*2 This product is designed for single phase 200 to 230VAC range.
*3 Values based on our measurement under the temperature and humidity conditions of +25℃ and 50%RH
*4 Excluding the terminal block and the filter guard
Contents of page
OC-12S-A200-CE
Cooling capacity
10/12 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 120 sq. : 1 pc. Screw for filter guards : 6 pcs.
Warning label (Rotating parts) : 1 pc. Instruction manual : 1 copy
Retaining washer : 4 pcs.
Warning label (Rotating parts) : 1 pc. Instruction manual : 1 copy
Retaining washer : 4 pcs.
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-120 | 1pc/set | OG-12 FIN | 1 set | OF-S1 | 1 pc. | FM-11938M -MV-00 |
1 pc. |
Cooling capacity
16/20 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 120 sq. : 2 pcs. Screw for filter guards : 8 pcs.
Warning label (Rotating parts) : 1 pc. Instruction manual : 1 copy
Retaining washer : 8 pcs.
Warning label (Rotating parts) : 1 pc. Instruction manual : 1 copy
Retaining washer : 8 pcs.
Maintenance parts
Filter guard | Filter guard | Replacement filter | Replacement fan | ||||
FFG-120 | 1pc/set | OG-28 FIN | 1 set | OF-S1 | 1 pc. | FM-11938M -MV-00 |
1 pc. |
Cooling capacity
35/42 W/K(50/60Hz)
A complete set of supply
BOXFAN : 1 unit Filter guard 150 sq. : 2 pcs. Screw for filter guards : 8 pcs.
Warning label (Rotating parts) : 1 pc. Instruction manual : 1 copy
Retaining washer : 8 pcs.
Warning label (Rotating parts) : 1 pc. Instruction manual : 1 copy
Retaining washer : 8 pcs.
Maintenance parts
Filter guard | Fin guard | Replacement filter | Replacement fan | ||||
FFG-150 | 1pc/set |
OG-37 FIN | 1 set | OF-S2 | 1 pc. | FM-15055M -MV-00 |
1 pc. |
Related products
Cautions
・Locate BOXFAN at least 150 mm away from adjacent components or walls to keep smooth air circulation between inside and outside the enclosure. Failure to this will lead to performance decline.
・Electrical connection should be made via an appropriate circuit breaker.
・This product is for indoor use only.
・Do not use this product in a place where flammable or corrosive gasses or any matters that can destroy insulation generate or permeate.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Make sure that the packaging is not damaged on delivery. Any packaging damage can lead to breakdown of the product. Please contact us immediately if any damage is found.
・Electrical connection should be made via an appropriate circuit breaker.
・This product is for indoor use only.
・Do not use this product in a place where flammable or corrosive gasses or any matters that can destroy insulation generate or permeate.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Make sure that the packaging is not damaged on delivery. Any packaging damage can lead to breakdown of the product. Please contact us immediately if any damage is found.