Non-fluorocarbon Series Slim & Short type
No obligatory inspection by Japanese law required.
Compact and lightweight body allows to install in a narrow space.
Compact and lightweight body allows to install in a narrow space.
Features
Type of mounting | Environment | Cooling method | Functions | Obligatory inspection by Japanese law | |||
Rececced *H300BCS only |
Duct kit (Option) | Adjustable louver (Accessory) *Except H300BCS |
Indoor | Compressor | Energy-saving mode | Display | N/A |
Certificates/Approvals
EU RoHS2 | China RoHS | CE | UL | CSA | PSE |
Model/Specification
Model | OCA- H300BCS-A200 |
OCA- H500BCS-A200 |
OCA- H500BCS-A220 |
OCA- H500BCS-A230 |
OCA- H500BCS-A240 |
OCA- H800BCS-A200 |
OCA- H800BCS-A220 |
OCA- H800BCS-A230 |
OCA- H800BCS-A240 |
|
Type of mounting | Lateral mounting | |||||||||
Cooling capacity *1 | 280/300W | 380/500W | 650/800W | |||||||
Rated voltage (50/60Hz) |
Single phase 200VAC | Single phase 200VAC | Single phase 220VAC | Single phase 230VAC | Single phase 240VAC | Single phase 200VAC | Single phase 220VAC | Single phase 230VAC | Single phase 240VAC | |
Current consumption *2 |
Rated | 1.4/1.2A | 1.4/1.3A | 2.1/2.1A | ||||||
Max. | 1.5/1.5A | 1.6/1.6A | 2.4/2.5A | |||||||
Starting current | 3.7/3.6A | 3.9/3.8A | 6.8/6.2A | |||||||
Power consumption *2 |
Rated | 230/240W | 250/260W | 290/300W | 300/310W | 310/320W | 400/400W | 460/460W | 480/480W | 500/500W |
Max. | 280/280W | 290/310W | 340/360W | 350/370W | 370/390W | 470/490W | 540/560W | 560/590W | 590/610W | |
Comp. motor output |
100W | 275W | ||||||||
Working temperature *3 |
+20 to +50℃ | |||||||||
Working humidity |
Not exceeding 85%RH, free from condensation | |||||||||
Noise (Charactristic A) |
61dB(A) | 64dB(A) | 63dB(A) | |||||||
Temp. setting range *3 |
+30 to+45℃ (Initial setting +35℃) | |||||||||
Display | Innter temperature/Alarm code/Operation lamp/Alarm lamp | |||||||||
Functions | Off-temperature alarm, Detection of abnormal heat dissipation, Detection of temperature sensor disconnection, Maintenance reminder,Forced cooling operation for inspection |
|||||||||
External output |
Alarm output 1a 240V 1.5A×2(COMMON) | |||||||||
Vibration withstand |
Vibration frequency 10 to 55Hz Amplitude 0.15mm Sweep cycle 10 times | |||||||||
Protection category *4 |
Internal circuit IP54 equivalent | |||||||||
Conformity to standards | EMC Directive | EN61000-6-2, EN61000-6-4 complaint | ||||||||
LV directive | EN60335-1, EN60335-2-40, EN62233 | |||||||||
Environment | RoHS2 | |||||||||
Refrigerant | R1234yf (140g) |
R1234yf (180g) |
R1234yf (220g) |
|||||||
GWP *5 | <1 | |||||||||
Color | Powder coating N8 corresponding, N4 corresponding | |||||||||
Dimensions(mm) | W200 ×H590 ×D200 |
W350×H450×D215 | W300×H730×D230 | |||||||
Weight | 14.0kg | 15.0kg | 18.0kg | 22.0kg | 25.0kg | 26.0kg |
*1Nominal value when both of internal and external temperatures are +35℃. By attaching the provided louver, the capacity reduces by up to 5%.
*2 Nominal values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max”.
*3 Use only within the specified temperature range.
*4 Except drain pipe
*5 By IPCC 5th Report 2013
※220VAC・230VAC・240VAC specification is made-to-order.
*2 Nominal values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max”.
*3 Use only within the specified temperature range.
*4 Except drain pipe
*5 By IPCC 5th Report 2013
※220VAC・230VAC・240VAC specification is made-to-order.
- Please contact us for other supply voltages than 200VAC.(Reference:Transformer for COOLCABI (Separate placement))
- Supply voltage should be within the fluctuation range of 10% from the rated voltage.
OCA-H300BCS-A200
Cooling capacity
280/300W(50/60Hz)
A complete set of supply
●COOLCABI:1 pc ●Fixing bolt:6 pcs ●Washer:6 pcs ●Spring washer:6 pcs
●Nut:6 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Nut:6 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
Consumable parts
Replacement fan | Replacement filter | |
Internal fan model | FM-11938P-A200-00 | CF-S1(2pcs/set) |
External fan model | FM-15038M-A200-00 |
Performance diagram
- Click the image to see a larger version.
- Please refer to "Model Selection for enclosure cooler" when you see the performance diagram.
Cooling capacity
380/500W(50/60Hz)
A complete set of supply
●COOLCABI:1 pc ●Fixing bolt:6 pcs ●Washer:6 pcs ●Spring washer:6 pcs
●Nut:6 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Adjustable louver:1 pc ●Screws for louver:4 pcs
●Nut:6 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Adjustable louver:1 pc ●Screws for louver:4 pcs
Consumable parts
Replacement fan | Replacement filter | |
Internal fan model | FM-15038P-A200-00 | CF-S1(2pcs/set) |
External fan model | FM-15038M-A200-00 |
Performance diagram
- Click the image to see a larger version.
- Please refer to "Model Selection for enclosure cooler" when you see the performance diagram.
Cooling capacity
650/800W(50/60Hz)
A complete set of supply
●COOLCABI:1 pc ●Fixing bolt:6 pcs ●Washer:6 pcs ●Spring washer:6 pcs
●Nut:6 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Adjustable louver:1 pc ●Screws for louver:4 pcs
●Nut:6 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Adjustable louver:1 pc ●Screws for louver:4 pcs
Consumable parts
Replacement fan | Replacement filter | |
Internal fan model | FM-15038P-A200-00 | CF-S1(2pcs/set) |
External fan model | FM-15038M-A200-00 |
Performance diagram
- Click the image to see a larger version.
- Please refer to "Model Selection for enclosure cooler" when you see the performance diagram.
Cautions
・Locate the unit so as to assure good ventilation and distance of at least 200mm from the walls or other units.
・Failure to this may degrade cooling performance of the unit and cause condensation.
・Setting temperature should be basically at 35℃. Avoid setting at an unnecessarily low value.
・Electrical connection should be made via appropriate circuit breakers.
・Do not use this product in the following places.
-A place where corrosive or flammable gases exist in the air, or where the insulation destruction occurs.
-A place where the product may be subject to shock or vibration.
・Make sure that electrical wiring work is done by qualified electrician.
・Check for damage on packaging when the product is delivered.
・Any packaging damage may be a cause of malfunction.Make sure that the packaging is not damaged on delivery and contact your supplier.
・Failure to this may degrade cooling performance of the unit and cause condensation.
・Setting temperature should be basically at 35℃. Avoid setting at an unnecessarily low value.
・Electrical connection should be made via appropriate circuit breakers.
・Do not use this product in the following places.
-A place where corrosive or flammable gases exist in the air, or where the insulation destruction occurs.
-A place where the product may be subject to shock or vibration.
・Make sure that electrical wiring work is done by qualified electrician.
・Check for damage on packaging when the product is delivered.
・Any packaging damage may be a cause of malfunction.Make sure that the packaging is not damaged on delivery and contact your supplier.