Go to global navigation

Read the article

Go to local navigation

Go to footer



Climate control equipment

Home > Climate control equipment > Indoor enclosure cooler "COOLCABI" lineup > Standard series Standard type Lateral mounting

Standard series Standard type Lateral mounting


Rich lineup in lateral mounting type.

COOLCABI スタンダードシリーズ

Features

Type of mounting Environment Cooling method Functions
Lateral/Rececced Duct kit (Option) Adjustable louver (Accessory) Indoor Compressor Energy-saving mode Display

Certificates/Approvals

EU RoHS2 China RoHS CE UL CSA PSE

Quick Selection

Model/Specification

Model OCA-S300BC-A100 OCA-S600BC-A100 OCA-S1000BC-A100 OCA-S1600BC-A100
Type of mounting Lateral mounting
Cooling capacity *1 250/300W 400/520W 750/900W 1300/1450W
Rated voltage(50/60Hz) Single phase 100VAC Single phase 100VAC Single phase 100VAC Single phase 100VAC
Current consumption *2 Rated 3.1/2.6A 4.1/3.9A 7.8/8.1A 8.9/9.2A
Max. 3.3/3.1A 5.1/5.3A 10.5/9.8A 11.2/11.4A
Starting current 7.0/6.7A 11.8/10.6A 24.3/20.2A 26.2/23.8A
Power consumption *2 Rated 265/250W 365/385W 665/770W 805/890W
Max. 310/300W 475/530W 1065/995W 1200/1135W
Comp. motor output 100W 250W 400W 470W
Working temperature *3 +20 to +50℃
Working humidity Not exceeding 85%RH, free from condensation
Noise(Charactristic A) 65dB(A) 65dB(A) 65dB(A) 68dB(A)
Temp. setting range *3 +30 to+45℃ (Initial setting+35℃)
Display Innter temperature/Alarm code/Operation lamp/Alarm lamp
Function Off-temperature alarm, Detection of abnormal heat dissipation, Detection of temperature sensor disconnection, Maintenance reminder, Forced cooling operation for inspection
External output Alarm output 1a 240V 1.5A×2(COMMON)
Vibration withstand Vibration frequency 10 to 150Hz, Acceleration 1.0G, Sweep cycle 20 times
Protection category *4 Internal circuit IP54 equivalent
Conformity to standards EMC Directive EN61000-6-2, EN61000-6-4 complaint
LV directive EN60335-1, EN60335-2-40, EN62233
Environment RoHS2
Refrigerant R134a(140g) R134a(180g) R407c(410g) R407c(510g)
GWP *5 1430 1770
Color Beige(5Y7/1 corresponding)
Dimensions(mm) W300×H500×D150 W300×H550×D200 W350×H900×D200 W390×H950×D220
Weight 16.0kg 18.0kg 33.0kg 36.0kg
*1 Nominal value when both of internal and external temperatures are +35℃. By attaching the provided louver, the capacity reduces by up to 5%.
*2 Nominal values at 35℃ temperature both inside and outside are indicated in “Rated” and values at 50℃ outside and 35℃ inside are indicated in “Max”.
*3 Use only within the specified temperature range.
*4 Except drain pipe
*5 By IPCC 5th Report 2013


Product lineup

OCA-S300BC-A100

OCA-S300BC-A100/A200

Cooling capacity

250/300W(50/60Hz)

A complete set of supply

●COOLCABI:1 pc ●Fixing bolt:4 pcs ●Washer:4 pcs ●Spring washer:4 pcs 
●Nut:4 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc 
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Adjustable louver:1 pc ●Screws for louver:4 pcs

Consumable parts

Replacement fan Replacement filter
Internal fan model FM-15038P-A100-00 CF-S1
(2pcs/set)
External fan model FM-15038M-A100-00

Performance diagram

能力グラフ

Dimensional drawing

外形寸法図

Mounting cutout

パネルカット図

Mounting view

取付図


OCA-S600BC-A100

OCA-S600BC-A100/A200

Cooling capacity

400/520W(50/60Hz)

A complete set of supply

●COOLCABI:1 pc ●Fixing bolt:4 pcs ●Washer:4 pcs ●Spring washer:4 pcs 
●Nut:4 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc 
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Adjustable louver:1 pc ●Screws for louver:4 pcs

Consumable parts

Replacement fan Replacement filter
Internal fan model FM-15038P-A100-00 CF-S1
(2pcs/set)
Extenal fan model FM-15038M-A100-00

Performance diagram

能力グラフ

Dimensional drawing

外形寸法図

Mounting cutout

パネルカット図

Mounting view

取付図


OCA-S1000BC-A100

OCA-S1000BC-A200

Cooling capacity

750/900W(50/60Hz)

A complete set of supply

●COOLCABI:1 pc ●Fixing bolt:6 pcs ●Washer:6 pcs ●Spring washer:6 pcs 
●Nut:6 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc 
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Adjustable louver:2 pcs ●Screws for louver:8 pcs

Consumable parts

Replacement fan Replacement filter
Internal fan model FM-15038P-A100-00 CF-S2
(2pcs/set)
External fan model FM-15038M-A100-00

Performance diagram

能力グラフ

Dimensional drawing

外形寸法図

Mounting cutout

パネルカット図

Mounting view

取付図


OCA-S1600BC-A100

OCA-H1600BC-A200

Cooling capacity

1300/1450W(50/60Hz)

A complete set of supply

●COOLCABI:1 pc ●Fixing bolt:6 pcs ●Washer:6 pcs ●Spring washer:6 pcs 
●Nut:6 pcs ●Packing:1 roll ●Drain hose:1 pc(2m) ●Terminal board:1 pc 
●Alarm explanation sheet:1 sheet ●Instruction manual:1 copy
●Adjustable louver:2 pcs ●Screws for louver:8 pcs

Consumable parts

replacement fan Replacement filter
Internal fan model FM-15038P-A100-00 CF-S3
(2pcs/set)
External fan model FM-15038M-A100-00

Performance diagram

能力グラフ

Mounting cutout

外形寸法図

Mounting cutout

パネルカット図

Mounting view

取付図


Option/Related products

Adjustable louver set

Cool air is directly blown to the heat source to prevent local temperature rise as well as creating uniform temperature in the enclosure.

Duck kit

Use of Duct kit allows cooling from a separately-placed COOLCABI.

Drain evaporator

Free from troublesome drain treatment and no more drain worrying about drainage problem.

Self-winding filter

くるくるフィルター

Roll filter is wound up automatically by motor.Free yourself from troublesome filter maintenance work.

Cautions

・Locate the unit so as to assure good ventilation and distance of at least 200mm from the walls or other units.
・Failure to this may degrade cooling performance of the unit and cause condensation.
・Setting temperature should be basically at 35℃. Avoid setting at an unnecessarily low value.
・Electrical connection should be made via appropriate circuit breakers.
・Do not use this product in the following places.
 -A place where corrosive or flammable gases exist in the air, or where the insulation destruction occurs.
 -A place where the product may be subject to shock or vibration.
・Make sure that electrical wiring work is done by qualified electrician.
・Check for damage on packaging when the product is delivered.
・Any packaging damage may be a cause of malfunction.Make sure that the packaging is not damaged on delivery and contact your supplier.
・Disposal of refrigerant and oil sealed in the cooling circuit should be dealt with only by professional services.