Heater type
Processes large amount of drain water up to 1000 ml/h
Features
Environment of use | Type of mounting | Processing method |
Indoor | Stationary/lateral mounting | Heater |
Certificates/Approvals
EU RoHS2 | China RoHS | CE | UL | CSA | PSE |
Model/Specifications
Model | OCJ-1201 | ||
Type of mounting | Floor standing or lateral mounting | ||
Processing capacity(*1) | 1000ml/h (at 30℃, 60%RH) | ||
Rated voltage | Single phase, 200VAC | ||
Power consumption | 4.5A | ||
Power consumption | 900W | ||
Working temperature | 0 to +50℃ | ||
Working humidity | 35 to 85%RH, free from condensation | ||
Error output | Overflow alarm (No voltage contact output) Contact capacity 200VAC 10A Resistance load | ||
Protective function | Double safeguard against excess temperature |
Thermostat (Auto-return at 45℃) | |
Thermal fuse (Fusing at 86℃) | |||
Overcurrent/leakage protection by earth leakage breaker | |||
Evaporation method | Direct evaporation method by heating water | ||
Conformity to standards | Environment | RoHS2 | |
Color | Beige(5Y7/1 equivalent) | ||
Dimensions (mm) | W400×H340×D260 | ||
Weight | 12.0kg |
- Supply voltage should be within the specified range with fluctuation not exceeding ±10%.
OCJ-1201
Processing capacity
1000ml/h
A complete set of supply
EVAPRO : 1 unit Fixing screw : 4 pcs. Nut : 4 pcs.
Washer : 4 pcs. Spring washer : 4 pcs. Hose band : 1 pc.
Instruction manual : 1 copy
Washer : 4 pcs. Spring washer : 4 pcs. Hose band : 1 pc.
Instruction manual : 1 copy
Maintenance parts
Replacement fan | Replacement filter |
FM-OCJ-1201 | OF-S1 |
Cautions
・This product is designed for processing drain water discharged from enclosure coolers. Do not use it for any other purposes.
・Locate EVAPRO at least 200 mm away from adjacent components or walls to keep smooth air circulation. Failure to this will lead to performance decline or adverse effect on other components.
・Do not use this product in a place where oil fumes, flammable/corrosive gasses or any matters that can destroy insulation generate or permeate.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Do not disassemble or tamper.
・Make sure that the packaging is not damaged on delivery. Any packaging damage can lead to breakdown of the product. Please contact us immediately if any damage is found.
・Locate EVAPRO at least 200 mm away from adjacent components or walls to keep smooth air circulation. Failure to this will lead to performance decline or adverse effect on other components.
・Do not use this product in a place where oil fumes, flammable/corrosive gasses or any matters that can destroy insulation generate or permeate.
・The site of use should be free from vibration and impact.
・Electrical works required for installation of this product should be done only by professionals or qualified personnel.
・Do not disassemble or tamper.
・Make sure that the packaging is not damaged on delivery. Any packaging damage can lead to breakdown of the product. Please contact us immediately if any damage is found.